Balangkas
Ang FN7-24(DR) panloob na HV load break switch ay nalalapat sa electric system na may 24kV rated voltage at three-phase AC 50/60Hz, para sa pagkonekta at pagsira ng load current at short circuit current.
Gamitin ang Kondisyon
A. Altitude: ≤1000m.
B. Temperatura sa paligid: -25℃~+40℃.
C. Kamag-anak na kahalumigmigan: pang-araw-araw na average ≤95%, buwanang average ≤90%.
D. Walang madalas na seryosong panginginig ng boses.
Pangunahing Parameter
HINDI. | Mga bagay | Yunit | Halaga |
1 | na-rate na boltahe | kV | dalawampu't apat |
2 | na-rate na dalas | Hz | 50 |
3 | kasalukuyang na-rate | A | 400, 630, 1250 |
4 | rated active load breaking current | A | 400, 630, 1250 |
5 | Na-rate na closed loop breaking current | A | 400, 630, 1250 |
6 | 5% rated active load breaking current | A | 20, 31.5, 62.5 |
7 | na-rate na cable charging breaking current | A | 10 |
8 | 1min power frequency makatiis ng boltahe: phase-to-phase, phase to earth/ fracture | kV | 50/60 |
9 | ang salpok ng kidlat ay lumalaban sa boltahe: phase-to-phase, phase to earth/ disconnecting fracture | kV | 125/145 |
10 | na-rate na maikling oras na makatiis sa kasalukuyang (thermal stability) | kA | 16, 20, 25 |
11 | na-rate ang tagal ng maikling circuit | s | 1 |
12 | rated peak makatiis sa kasalukuyang | kA | 40, 50, 63 |
13 | rated short circuit paggawa ng kasalukuyang | kA | 40, 50, 63 |
14 | mekanikal na buhay | beses | 2000 |
Pangkalahatang Pagguhit
FN7-24D
FN7-24R